Balanced Pressure Thermostatic Steam Traps are equipped with a capsule element, which controls the discharge of condensate depending on the temperature. The capsule contains a special liquid, whose saturation temperature at a given pressure is always lower than that of the water. It ensures a very accurate functioning of the steam trap and is self-adjusting.
The discharge characteristic follows the saturation curve independent from pressure changes and the condensate load.
Series D MIYAWAKI steam traps can be delivered with 3 different capsule types:
    - Types H & C discharge hot condensate at approximately 5°C (9°F) below saturation temperature
    - Type L discharges hot condensate at approximately 15°C (27°F) below saturation temperature
 
      Thermostatic Steam Traps with "Dia-Thermo" membrane capsules
 
Specification
Model Available
Sizes
Available
Connections
Max.Operating
Pressure
MPa (psig)
Max.Operating
Temperature
°C (°F)
Body and
Cover Material
Download
DL1 1/2"– 1" Screwed Rc & NPT 2,1 (305) 220 (428) Stainless Steel Thermostatic Steam Traps with "Dia-Thermo" membrane capsules
(924 KB)
DF1 1/2" – 1" Screwed
Rc & NPT

Socket weld
JIS, ANSI, DIN

Flanged
JIS, ANSI, DIN
2,1 (305) 235 (455) Forged Steel
DV1 with bypass 1/2" – ¾" Screwed Rc & NPT 1,0 (145) 184 (363) Stainless Steel Thermostatic Steam Traps with "Dia-Thermo" membrane capsules
(533 KB)
DC1 1/2" – 1" Screwed Rc & NPT 2,1 (305) 220 (428) Stainless Steel
DX 38 mm Tri-Clamp 0,5 (73) 160 (320) Stainless Steel Thermostatic Steam Traps with "Dia-Thermo" membrane capsules
(924 KB)

Inverted bucket steam traps discharge the condensate near the saturation temperature.

Applications:

steam main drips, heat exchangers and all other applications in the petrochemical, food, textile, pharmaceutical and other industries where the condensate must be removed quickly.
      Cast Iron Inverted Bucket Steam Traps
Specification

Model Available
Sizes
Available
Connections
Max.Operating
Pressure
MPa (psig)
Max.Operating
Temperature
°C (°F)
Body and
Cover Material
Max.
Capacity
kg/h(lb/h)
Download
ES5 1/2" – 1" Screwed
Rc & NPT
1,6 (230) 350 (662) Ductile Cast Iron 300 (660) Cast Iron Inverted Bucket Steam Traps
(555 KB)
ES8N 1/2"–1" Screwed
Rc & NPT

Flanged
JIS, ANSI, DIN
1,6 (230) 350 (662) Ductile Cast Iron 570 (1254)
ES10 3/4"– 1½" Screwed
Rc & NPT
1,6 (230) 220 (428) Cast Iron 900 (1,980)
ES10F
1/2" – 2"
Flanged
JIS, ANSI, DIN
1,6 (230) 220 (428) Cast Iron 900 (1,980)
ES12N 1/2" – 2" Flanged
JIS, ANSI, DIN
1,6 (230) 220 (428) Cast Iron 1700 (3,740
Inverted bucket steam traps discharge the condensate near the saturation temperature.

Applications:

steam main drips, heat exchangers and all other applications in the petrochemical, food, textile, pharmaceutical and other industries where the condensate must be removed quickly.
      Cast Iron Inverted Bucket Steam Traps
Specification:

Model Available
Sizes
Available
Connections
Max.Operating
Pressure
MPa (psig)
Max.Operating
Temperature
°C (°F)
Body and
Cover Material
Max.
Capacity
kg/h(lb/h)
Download
ER105 3/4" – 1 ½" Screwed
Rc & NPT
0,7 (100) 220 (428) Cast Iron 2050 (4,510) Cast Iron Inverted Bucket Steam Traps
(511 KB)
ER105F DN15 - DN50 Flanged
JIS, ANSI, DIN
ER110 DN15 - DN50 Flanged
JIS, ANSI, DIN
1,2 (174) 220 (428) Cast Iron 2450 (5,390)
ER116 DN15 - DN50 Flanged
JIS, ANSI, DIN
1,6 (230) 300 (572) Ductile
Cast Iron
2850 (6,270)
ER120 DN40 - DN65 Flanged
JIS, ANSI, DIN
1,6 (230) 220 (428) Cast Iron 9000 (19,800
Thermodynamic disc steam traps discharge the condensate near the saturation temperature. The traps may operate until a back pressure of 80% of the inlet pressure, but for smooth operation it is recommended that the back pressure does not exceed 50% of the inlet pressure.

Applications:

steam main drips, heat exchangers and all other applications in the petrochemical, food, textile, pharmaceutical and other industries where the condensate must be removed quickly
         

MIYAWAKI Air Traps are designed for continuous discharge of condensate from air piping, receiver tanks, gas and compressed air systems.

Depending on the operating conditions and applications a wide range of various types of air traps is available. Most of the traps can be fitted with a pressure - balancing line to ensure air can escape from the trap body to prevent air locking. Pressure-balancing lines are usually not necessary, if the air trap is installed directly below the equipment to be drained or if the trap is installed vertically.

MIYAWAKI offers different seat materials and various body materials (including stainless steel) for draining special gas applications.

MIYAWAKI Air Vents are designed for pipe lines or industrial equipment to remove troublesome air automatically from them.
      Air Traps - Series A 
 
Specification
Model Name Type
of Trap
Available
Sizes
Available
Connections
Max.
Operating
Pressure

MPa (psig)
Max.
Operating
Temperature

°C (°F)
Body
and
Cover Material
Max.
Capacity

kg/h (lb/h)
Download
AG11 Ball Float 1/2", 3/4" Screwed
Rc & NPT
0,97 (140) 100 (212) Cast Iron FC 250
(GG 25)
1.400
(3,080)
Air Traps and Air Vents
(538 KB)
AG12 3/4", 1"
AG29 DN15 – DN25 Flanged JIS, ANSI, DIN 0,97 (140) 300 (572) Ductile
Cast Iron (GGG 40.3)
1.500 (3,300) Air Traps and Air Vents
(492 KB)
AGH29 DN15 – DN50 Flanged JIS, ANSI, DIN

Socket weld JIS, ANSI, DIN
2,9 (420) 350 (662) Cast
Steel
(GS-C 25)
AGU29 DN15 – DN50   1,6 (230) 350 (662) Stainless
Steel
AGC1V 1/2"-1"
vertical instalation
Screwed
Rc & NPT

Flanged JIS, ANSI, DIN
Socket weld JIS, ANSI, DIN
2,1 (305) 350 (662) Stainless
Steel
  Air Traps and Air Vents
(538 KB)
AE8 Inverted
Bucket
1/2" – 1"
DN15  – DN25
Screwed
Rc & NPT

Flanged JIS, ANSI, DIN
0,97 (140) 220 (428) FCD450 (GGG 40.3) 470 (1,034) Air Traps and Air Vents
(530 KB)
AV Thermo-
dynamic
1/2" – 1" Screwed
Rc & NPT
0,97 (140) 150 (302) Cast Iron FC 250
(GG 25)
1.400 (3,080)


Installation Example:
Current Pageid = 552